Shore Power & Worldwide Yachting

The availability of shore power is both a blessing and a curse. It is convenient to supplement systems when in a marina or harbor. At the same time, the plethora of voltages, frequencies, and capacities is confusing. Vanguard is built to cruise worldwide and should encompass the flexibility to maximize what is achievable, but that's easier said than done. Have you ever started a project then wished you had not? That was us and "shore power", so many false dawns along the way.


The illustration below is the our shore power system, there follows the story of how we understood the issues and how we arrive at this solution.

Yacht power electrical system including single and three phase shore power connections with galvanic isolation. Fully independent of frequency or input voltage worldwide.


The Short Version

Accept shore power from anywhere in single or three phase at any voltage or frequency. Convert everything to DC, charge your batteries. Accept some inevitable transmission losses along the way and move on. Feed solar direct to 24VDC consumers to minimize transmission losses when at sea.


The Problem

Our XPM-78 explorer yacht, Vanguard, has some unique machinery. A diesel electric hybrid drive and huge power batteries. To summarize:*

  • 230 VAC 50Hz Single phase

  • 400 VAC 50Hz Three-phase plus neutral

  • 24VDC (with the occasional 12VDC for Comms and Nav gear)

These feed into systems containing:

  • 20 kWh of LiFePO house batteries at 24 VDC

  • 120 kWh of LiFePO power batteries at nominally 600 VDC

In turn, the available power sources are:

  • 6.5 kW of solar panels at peak capacity

  • Two by 90kW 50Hz alternators (hybrid drives operated decoupled from the propellers and at full engine speed)

  • Shore power vis:

Single Phase: 120 VAC 60 HZ 30 amps approx

240 VAC 60HZ split phase (2 phase and floating neutral) 50 amps

230 VAC 50 HZ 50/100 amps

Three-phase: 208 VAC 60 HZ Three-phase 100 amps (combined)

400 VAC 50 HZ Three-phase 100 amps (combined)


One last complication in the mix is that we need galvanic protection for our aluminum hull utilizing an Isolation Transformer. The device prevents earth currents from circulating between ship and shore (for safety and to limit corrosion).


Have you ever seen a circus trick known as "plate spinning"? Lots of moving pieces in the air at the same time? Well, that is how this felt at the time!


Solving for Single Phase Systems. With a multifaceted problem, start by simplifying the issues. The supply frequency 50 and 60 Hz systems that are incompatible at the AC level. Also, an isolation transformer will not change the frequency. All single-phase power input runs through the same dual frequency Victron isolation transformer and charging system to feed the house batteries. A slight increase in conversion losses results, but we felt it worthwhile to pursue simplicity. 6.5 kW peak of Solar in-feed also charges the house batteries and powers the 24VDC system whenever the sun shines.

Victron 3600kW Isolation Transformer.


Solving for our Three Phase System

The problem remained of how to cope with three-phase supplies? I refer you here to the circuit diagram on the top of the page. We wanted to maximize the advantage of a beefed-up power source to charge two by 60kWh power batteries.